LT Power Cables

SUPEREX FR (Flame Retardant)

thumbnail

Description

India’s 1st REACH and RoHS Compliant Cable | Flame Retardant Cable.

REACH,CE,ROHS and CPR Compliant.

Anti-Rodent, Anti-Termite

More than 101% Conductivity

Application

Suitable for wiring in all types of residential and commercial infrastructure, where fire and electrical safety is utmost important.

Technical Data

Approvals : IS 694 marked, FIA/TAC.

Voltage Grade : Up to and including 1100V

Conductor : Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility. The strands are twisted with high precision to impart circularity for the conductor.

Insulation : Specially formulated flame retardant PVC insulation is used. The FR property retards the propagation of flame without compromising safety.

Insulation Conformity : IS 5831, Type A/D FR 70oC

Colours : Red, yellow, blue, black, green, grey & white.

Marking : The cables are printed with marking of ‘SUPEREX FR' from 1 Sq. mm to 4 Sq. mm & "RR KABEL FR" for all other sizes.

Packing : 90 mtr. coil is packed in protective cartons upto size 6 Sq. mm. Project packing of 180 mtr. also available.

Cable Design Parameters

Please complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – grey, 07 – white.

Part Number Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Number *Nominal Dia. of Strands Approx. Overall Diameter (mm) Max. DC Conductor Resistance at 20°C (Ω/km) Current Rating (Amps)
Casing Concealed
01010102xx20 0.75** 0.6 24/0.2 2.3 26.0 9 8
01010103xx20 1 0.7 14/0.3 2.7 18.1 14 13
01010104xx20 1.5 0.7 22/0.3 3.0 12.1 18 16
01010105xx20 2.5 0.8 36/0.3 3.7 7.41 24 20
01010106xx20 4** 0.8 56/0.3 4.1 4.95 30 26
01010107xx20 6** 0.8 84/0.3 4.6 3.30 38 33
01010108xx20 10** 1.0 140/0.3 7.0 1.91 52 45
01010109xx20 16** 1.0 126/0.4 8.1 1.21 70 60

*Conductor as per IS 8130

** Insulation Type D as per IS 5831

Properties

Test Test Method Values
Limited Oxygen Index IS 10810 P-58 > 29%
Limited Temp. Index IS 10810 P-64 >250 °C