LT Power Cables

PVC/PVC 3 CORE SUBMERSIBLE FLAT CABLE

thumbnail

Application

The PVC insulated and sheathed 3 core flat cables are mainly used in pump connections. They are also used in many industrial applications.

The sheath is specially made out to resist tough and difficult outdoor conditions & excellent resistant to water.

Technical Data

Approvals : IS 694 marked, FIA/TAC

Conductor : Electrolytic grade annealed copper

Core Colour : Red, yellow (centre core), blue

Sheath Colour : Black

Voltage grade : Upto and inducting 1100V

Packing : Standard packing of 100 mtr. in coils. Longer length available on request.


Variants Available

Product Type Speci?cations
PVC 70°C IS 694, IS 8130 Class 2(1.5 & 2.5 Sq. mm), for others class 5, IS 5831 Type A insulation & ST-1 sheath.
HR 85°C IS 694, IS 8130 Class 2(1.5 & 2.5 Sq. mm), for others class 5, IS 5831 Type C insulation & ST-2 sheath.

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘y’) for the cable type 1 – PVC 70°C, 3 – PVC HR 85°C.

Part number Conductor construction Conductor resistance at 20 °C (Ω/km) Max. Nom. Insulation thickness (mm) Nominal sheath thickness (mm) Approx. overall dimensions (W X H) (mm) +/- 0.5 mm Current carrying capacity (Ampere)
Cross sectional area (Sq. mm) No./Max. dia of strands (mm)
0118110102y1 0.5 16/0.2 39.0 0.6 0.9 9.60 X 4.90 4
0118110202y1 0.75 24/0.2 26.0 0.6 0.9 10.5 X 5.20 7
0118110302y1 1 32/0.2 19.5 0.6 0.9 11.0 X 5.40 12
0118110402y1 1.5* 22/0.3 12.1 0.6 0.9 12.0 X 5.6 18
0118110502y1 2.5* 36/0.3 7.41 0.7 1.0 13.0 X 6.2 24
0118110602y1 4 56/0.30 4.95 0.8 1.0 15.3 X 7.1 28
0118110702y1 6 84/0.30 3.30 0.8 1.1 19.2 X 8.4 36
0118110802y1 10 140/0.30 1.91 1.0 1.4 24.2 X 10.4 48
0118110902y1 16 126/0.40 1.21 1.0 1.4 29.0 X 12.4 64
0118111002y1 25 196/0.40 0.78 1.2 2.0 36.5 X 15.7 80
0118111102y1 35 276/0.40 0.554 1.2 2.0 40.5 X 17.2 100
0118111202y1 50 396/0.40 0.386 1.4 2.2 46.5 X 19.3 130
0118111302y1 70 360/0.50 0.272 1.4 2.2 52.0 X 21.0 192
0118111402y1 95 480/0.50 0.206 1.6 2.4 61.0 X 24.5 230

*Conductor configuration offered for 1.5 Sq mm-22/0.3 mm, 2.5 Sq mm – 36/0.3 mm (max.), class 2 as per IS 8130

Ambient Temperature (°C) Derating Factor
25 1.25
30 1.16
35 1.09
40 1.00
45 0.90
50 0.81
55 0.74
60 0.68