LT Power Cables

HALOGEN-FREE H07Z-R-6491B

thumbnail

Application

The cables are suitable for conduit wiring , especially in installations where fire, smoke and toxic fumes create potential threat.

Standard

BS EN 50525-3-41.

Technical Data

Voltage Rating : Uo / U - 450 / 750V

Harmonized Code : 1.5 mm.sq to 630 mm.sq stranded class 2 - H07Z-R Fixed installation -30°C to +70°C

Temperature Range : -15°C to 90°C Minimum Bending Radius

Upto 10 mm2 : 3 X Overall Diameter. 16 & 25 mm.sq : 4 X Overall Diameter. Above 25 mm.sq : 5 X Overall Diameter.

Cable Construction

Conductor : Plain annealed copper conductor 1.5 mm.sq to 630 mm.sq stranded Cl. 2 complying with EN 60228.

Insulation : LSZH (Low Smoke Zero Halogen) Type EI5 according to BS EN 50363-5

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey

Part Number Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approx. Net Weight (kg/km)
01130101xx60 1.5 0.70 2.70 3.40 19
01130102xx60 2.5 0.80 3.30 4.10 33
01130103xx60 4 0.80 3.80 4.70 50
01130104xx60 6 0.80 4.30 5.40 74
01130105xx60 10 1.00 5.60 7.00 126
01130106xx60 16 1.00 6.40 8.00 184
01130107xx60 25 1.20 8.10 10.10 295
01130108xx60 35 1.20 9.00 11.30 375
01130109xx60 50 1.40 10.60 13.20 510
01130110xx60 70 1.40 12.10 15.10 710
01130111xx60 95 1.60 14.10 17.60 950
01130112xx60 120 1.60 15.60 19.40 1240
01130113xx60 150 1.80 17.30 21.60 1530
01130114xx60 185 2.00 19.30 24.10 1800
01130115xx60 240 2.20 22.00 27.50 2500
01130116xx60 300 2.40 24.50 30.60 2990
01130117xx60 400 2.60 27.50 34.30 3860
01130118xx60 500 2.80 30.50 38.20 4900
01130119xx60 630 2.80 34.00 42.50 6370