LT Power Cables

A2XY / 2XY-4 CORE

thumbnail

Cable Construction

1.1 kV (A.C) & 1.5 kV (D.C ) to Earth

4 cores AL /CU conductor, XLPE insulated, unarmoured cables as per IS 7098 Part - 1.

Conductor : AL up to 10 Sq. mm conductor are solid Cl. 1 as per IS 8130. And above 10 Sq. mm conductor are stranded compacted shape Cl. 2 as per IS 8130

In CU 4 & 6 Sq. mm conductor are solid Cl. 1 or stranded Cl.2 as per IS 8130. 10 Sq. mm conductor is stranded Cl. 2 round as per IS 8130. Above 10 Sq. mm conductor are stranded compacted shaped Cl. 2 as per IS 8130

Insulation : Crosslinked polyethylene (XLPE)

Core Color : Red, yellow, blue

Inner Sheath : PVC / PVC tape as per IS 7098 (P - 1)

Outer Sheath : PVC Type ST - 2 as per IS 5831 (Option : FR Type / FRLS Type)

Cable Color : Black (Options : Any other color as per requirement)

Cable Design Parameters

While ordering, in addition to the part number the following details shall also be advised:

Conductor Type (Aluminium or Copper) and class of conductor (Cl. 1 or 2).

Sheath Type – PVC Type ST – 2 (FR or FRLS).

Part Number Nominal Cross Sectional Area(Sq. mm) Nominal Thickness of Insulation(mm) Minimum Thickness of Inner Sheath(mm) Nominal Thicknessof Outer Sheath(mm) Approx.Overall Diameter(mm) Approx. Net Wt. of Cable (kg/km)
AL Cable A2XY CU Cable 2XY
111700400004 4 0.7 0.3 1.8 16 225 340
111700400006 6 0.7 0.3 1.8 17 315 480
111700400010 10 0.7 0.3 1.8 19 370 640
111700400016 16 0.7 0.3 1.8 20 440 840
111700400025 25 0.9 0.3 2.0 24 650 1290
111700400035 35 0.9 0.3 2.0 26 780 1685
111700400050 50 1.0 0.3 2.0 29 985 2190
111700400070 70 1.1 0.4 2.2 34 1380 3090
111700400095 95 1.1 0.4 2.2 37 1685 3980
111700400120 120 1.2 0.5 2.4 41 2125 5130
111700400150 150 1.4 0.5 2.6 45 2630 6230
111700400185 185 1.6 0.5 2.8 50 3230 7830
111700400240 240 1.7 0.6 3.0 56 4080 9980
111700400300 300 1.8 0.7 3.2 63 5030 12030
111700400400 400 2.0 0.7 3.6 70 6385 15980
111700400500 500 2.2 0.7 3.8 79 7980 19985
111700400630 630 2.4 0.7 4.0 88 9985 25985