LT Power Cables

SINGLE CORE FIRE RESISTANT

thumbnail

Application

These cables are designed for installations in trunking and conduits where a fire situation may pose a major hazard. Circuit integrity is maintained and to achieve optimum performance such cables should be installed in metal conduits.

Standard

Adapted to EN 50525-3-41

Technical Data

Voltage Rating : 450 / 750 V

Operating Temperature : -20°C to + 90°C (the cable should not be flexed when the temperature is below 0°C)

Minimum Bending Radius : 8 x Overall diameter

Cable Construction

Construction : Stranded plain annealed copper conductor to BS EN 60228, class 2.

Insulation : Mica (fire resistant) tape covered by an extruded layer of cross - linked low smoke zero halogen (LS0H), insulating compound

*Sheathed version also available. Details available on request.

Circuit Integrity for installation in metal conduits : BS 6387 categories C, W & Z (when applied to a single cable) Exceeds IEC 60331 - 3 hours at 750°C - when the test temperature was increased to 950°C, equivalent to BS 6387 category C

Acid Gas Emission : IEC 60754-1, BS EN 50267-2-1

Smoke Emission : IEC 61034, BS EN 50268

Flame Propagation : EN 60332-1, EN 60332-3, BS EN 50265, BS EN 50266

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required : 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 09 – brown, 12 – grey.

Part Number Nominal CrossSectional Area (Sq. mm) Insulation Thickness (mm) Max. Overall Diameter (mm) Approx. Cable Weight (kg/km)
10040101xx60 1.5 0.7 3.8 32
10040102xx60 2.5 0.8 4.5 43
10040103xx60 4 0.8 5.0 55
10040104xx60 6 0.8 5.5 85
10040105xx60 10 1.0 7.0 146
10040106xx60 16 1.0 8.0 198
10040107xx60 25 1.2 9.7 320
10040108xx60 35 1.2 10.8 410
10040109xx60 50 1.4 13.3 549
10040110xx60 70 1.4 15.1 770
10040111xx60 95 1.6 17.5 1140
10040112xx60 120 1.6 19.2 1425
10040113xx60 150 1.8 21.2 1720
10040114xx60 185 2.0 23.6 2155